How to check a pressure relief valve for leakage without shutting the line down
A relief valve can pass across its seat while the line stays in service. How to find the leak with ultrasound at points on the body and the discharge pipe, how steam differs from gas and liquid, and what to do with the result.
In this article
SDT340 on the outlet pipe of a spring-loaded relief valve: the sensor goes on the pipe right after the valve. The scene is recreated from the manufacturer image of the instrument.
KEG TRKAuthor: Georgy Cheredeev, Technical Director, KEG TRK · Updated: November 24, 2026 · How we prepare our content
A leaking relief valve can be found on a live line. Press the contact sensor of an ultrasonic detector against the valve body and the discharge pipe, and compare the level with an identical valve under the same conditions. A steady turbulent-flow noise means the medium is passing across the seat. This reading does not check the set pressure.

AI-generated illustration: a spring-loaded relief valve and a discharge pipe. This is not a photograph from a customer site.
How does a leaking relief valve differ from a leaking shut-off valve?
A gate or isolation valve has a handwheel or an actuator, so its closed position is set from outside. The method for such valves is described in how to check a gate or control valve for leakage with ultrasound, and an example of the level rising on the body is in a passing gate valve: how the ultrasound level rises. In a relief valve the seat is held by a spring, and the closing force cannot be adjusted from outside. Three differences follow.
- A pressure difference is almost always there. The valve inlet is at process pressure and a relief line sits behind the seat. The requirement that a pressure difference must exist is met by itself, but the leakage depends on the operating condition.
- Leakage grows with pressure. Spring valves tend to simmer when the operating pressure approaches the set pressure, and with a small margin the seat is less tight. According to Allied Valve (Safety-Relief Valve FAQ, 2009) such simmering is typical at 80-90 % of the set pressure, and a margin of at least 10 % between operating and set pressure is advised, while 20 % gives better seat tightness.
- There is a second check point. Behind the valve is the discharge pipe, and it shows what actually got through the seat. For a shut-off valve this is just "downstream"; for a relief valve it is a separate object of observation.
Where should the sensor go on a relief valve?
The three-point method from the shut-off valve article applies here too, but the points differ.
- Inlet nozzle or pipe before the valve. This is your background: process noise, pumps, neighbouring valves.
- Valve body at the seat. Place the sensor on the body or on a flange, not on the spring bonnet and not on fasteners that vibrate.
- Discharge pipe right after the valve. Preferably on a straight section near the outlet flange, not at the common header.
- Discharge header. Needed only if the valve discharges into a shared line: it shows whether the header is noisy because of other valves.
Keep the same point, angle and contact pressure, preferably with a magnetic base. Repeatability matters more than the absolute value, because there is no single dBµV limit for all valves.
Equipment covered in this article

SDT340 - Advanced Ultrasound Detector
The most advanced ultrasound detector for collecting, analysing and trending data
How do you carry out the check step by step?
- Prepare a list of valves with tag numbers, medium, set pressure and line condition. Obtain permission and agree a safe position, especially at height and near hot surfaces. Do not stand in front of the outlet.
- Record the operating pressure at the time of the reading. For a spring valve it matters how close it is to the set pressure.
- Press the contact sensor of the detector against the inlet pipe, then the body, then the discharge pipe. The instrument is an SDT340 or SDT270. Listen on the headset and record the level.
- Compare the body with the discharge pipe and the inlet. If the outlet side is clearly louder, the noise is made by the flow that got through the seat.
- Repeat the reading on a neighbouring valve of the same type under the same conditions. This is your reference.
- Check the temperature of the discharge pipe with a non-contact thermometer: in steam and hot service a rise supports the finding and helps to rule out foreign noise.
- Log the result: valve number, condition, pressure, points, levels, photos. UAS3 software is suited to trends.
How do steam, gas and liquid differ?
| Medium | What you hear | What else to check |
|---|---|---|
| Steam | Steady noise that carries far along the discharge pipe | Heating of the discharge pipe, haze at the outlet, steam loss. For steam equipment see steam, valves and energy |
| Gas | Even hiss, depends on pressure and composition | Discharge to a flare header: noise from the header and from other valves masks the picture |
| Liquid | The noise can resemble steam | Compare with known water and steam lines. According to the Ultraprobe manual (UE Systems), lowering the sensitivity and comparing helps |
Any medium creates turbulence when it passes, and the level grows with flow. So do not compare decibels between steam, gas and liquid: compare a valve with an identical valve in the same medium.
How do you rank the leaking valves?
The dBµV level alone is not enough for ranking. Assess together:
- the hazard of the medium and where it goes: to atmosphere, to a flare, to a drain;
- the rise of the signal compared with the previous reading and with the reference valve;
- how close the operating pressure is to the set pressure;
- the loss: steam, gas or product that escapes continuously;
- repair availability: the nearest shutdown, a spare valve.
A valve with a rising signal in a hazardous medium goes first, even if its level is not the highest.
What should be done after a leak is found?
- Do not remove the valve on a live line. Repair is possible only after isolation and depressurisation under the plant procedure.
- Add the valve to the plan of the nearest shutdown. The overhaul usually includes seat inspection, lapping or replacement of the part, and a bench test.
- After the repair, test the set pressure and seat tightness on a bench under the plant procedure. The test conditions and the permitted leakage are set by the standard (for example API STD 527) and the plant method, not by ultrasound.
- After installation repeat the reading at the same points and compare with the value before the repair.
In Kazakhstan the procedure and frequency of relief valve checks are set by industrial safety requirements and the plant regulations. Confirm them with the person responsible for the hazardous facility: this article does not replace them.
What are the limits of the method?
- Ultrasound shows that the medium is passing across the seat. It does not measure the set pressure and does not replace the bench test.
- Silence does not prove tightness. A small flow may give no noticeable signal, and thick insulation or poor access weakens it. No noise behind the valve does not necessarily mean the valve is closed.
- The leak flow cannot be calculated from the level. A loss estimate needs other data.
- Foreign noise (hose-down, steam whistles, pipe vibration, neighbouring valves on a shared header) causes false alarms. That is why valves are compared and readings repeated.
- Valves with a very small difference between operating and set pressure may simmer in normal operation. Assess the operating condition first.
The general method for valve inspection and other ultrasound tasks is on the page Ultrasonic valve inspection and in the ultrasonic inspection guide. For the pneumatic actuator of a control valve, an external air leak is found with a different method: how to find a leak in a pneumatic cylinder and actuator.
Request an instrument selection for relief valve inspection
Sources
- Allied Valve (Jim Knox), Safety-Relief Valve FAQ, Valve Magazine, 2009: simmering of a spring valve at 80-90 % of the set pressure, margins of 10 % and 20 %.
- UE Systems, Valve Leak Inspection with Ultrasound, BIC Magazine: relief valve inspection, checking the discharge line with a non-contact thermometer.
- Reliabilityweb, Ultrasonics: a sound concept: no noise behind a valve does not mean it is closed.
- Patent US 7890276, Pressure relief valve monitoring: an acoustic sensor on the discharge pipe at the valve outlet and temperature sensors; false alarms from hose-down, steam whistles and pipe vibration.
- SDT Ultrasound Solutions: valve inspection materials, product pages SDT340 and SDT270. The method does not replace the requirements of valve test standards (for example API STD 527).
See also
Frequently asked questions
Equipment in this article
KEG TRK quotes prices and delivery times to Kazakhstan on request. We will prepare a commercial offer for your application.

SDT340 - Advanced Ultrasound Detector
The most advanced ultrasound detector for collecting, analysing and trending data

SDT270 — SDT Ultrasound Detector and Data Collector
Handheld SDT ultrasound data collector: 2 channels, up to 100 kHz bandwidth, built-in IR thermometer and laser tachometer, ICP accelerometer input, signal recording for…
Read also
11/23/2026
A passing valve: how the ultrasound level rises at the body
A short animation based on SDT data: how the ultrasound level at the body rises when a gate valve stops being fully closed. How to read the rise and what to compare it with.
10/22/2026
How to check a gate or control valve for leakage with ultrasound: the three-point method
How to find internal leakage across a closed valve without opening the pipe: SDT270 or SDT340 with a contact sensor, readings at the inlet, body and outlet, and an example from a compressor station.
10/22/2026
Which sensor to choose for SDT: contact, airborne, flexible or parabolic