Supply in Kazakhstan
KEG TRK supplies SF6 gas analysis solutions (Cambridge Sensotec) across Kazakhstan: Almaty, Astana, Karaganda, Ust-Kamenogorsk, Aktobe and other regions. Official warranty, monitoring system design, installation, commissioning and personnel training.
Key features
Applications and resources
Industry solutions, landing pages and articles about Rapidox 6100 QU4D Multi-Gas Pumpback — SF6, C4-FN, C5-FK and Clean Air Analyser
Where it is used
Typical tasks
- Utilities with mixed GIS fleets
- Circuit breakers and GIS on SF6 and alternative gases
- Gas-insulated transformers
- Incoming cylinder inspection
- Service contractors working on multiple OEMs' equipment
Documentation
Official manufacturer PDF documents. Key specifications are also published on this page.
Need a price with delivery in Kazakhstan? We will prepare a quotation for your task.
Configurable Rapidox 6100 QU4D platform for comprehensive gas quality analysis in substations and GIS.
Overview
The Rapidox 6100 QU4D Multi-Gas Pumpback is a portable analyser from the British company Cambridge Sensotec for gas-insulated electrical equipment. It handles four insulation types: SF6, C4-FN (g3) and C5-FK (AirPlus) mixtures, and Clean Air. For a utility where older SF6 GIS sits next to new SF6-free apparatus, it is one instrument instead of several.
In one cycle the analyser measures gas purity, moisture and decomposition products. Afterwards the sample is returned to the equipment, so no gas is lost or released.
Supported mixtures
| Insulation | Mixture | Measured |
|---|---|---|
| SF6 | SF6 and SF6 + CF4 | SF6 purity, H₂O, SO₂, HF, H₂S, CO, CF4 |
| C4-FN (g3) | C4-FN + CO₂ / O₂ | C4-FN, CO₂, O₂, H₂O, CO |
| C5-FK (AirPlus) | C5-FK + CO₂ | C5-FK, CO₂, H₂O, CO |
| Clean Air | N₂ + O₂ | O₂ / air, H₂O, NO₂ |
In each mode the instrument measures up to eight parameters at once. The sensor set is chosen at ordering and can be extended later.
How a measurement works
- Connect the instrument to the compartment or cylinder through a Rectus-style fitting (DN8 and DN20 adaptors supplied) and select the gas type.
- When switching gas, the instrument purges and sends the remainder to a recovery bag.
- The Rapidox draws a small amount of pressurised gas; a vacuum purge and internal storage keep air out of the sample.
- All parameters are measured simultaneously; a stable reading takes a few minutes.
- The compressor returns the gas at up to 10 bar. Results are logged and printed.
Sensors and ranges
| Parameter | Range | Accuracy | Sensor type | Calibration |
|---|---|---|---|---|
| SF6 | 0–100 % | ±0.5 % | IR or density | 12–24 months |
| H₂O (dew point) | -60 to +20 °Cdp (10–24,000 ppmV) | ±2 °Cdp | polymer | 12 months (sensor exchange) |
| SO₂ | 0–100, 0–150, 0–500 or 0–2000 ppm | ±2 % FS | electrochemical | 12–24 months |
| HF | 0–10 or 0–20 ppm | ±2 % FS | electrochemical | 12–24 months |
| CF4 | 0–80 % | ±1 % of reading | calculated | not required |
| H₂S | 0–100 ppm | ±2 % FS | electrochemical | 12–24 months |
| CO | 0–500, 0–1000, 0–2000 or 0–5000 ppm | ±2 % FS | electrochemical | 12–24 months |
| Air / O₂ / N₂ | 0–100 % air, 0–30 % O₂ | ±1 % FS | electrochemical | 12–24 months |
| CO₂ | 0–100 % | ±0.5 % | IR | 12–24 months |
| C4-FN / C5-FK | 0–20 % | ±0.5 % | — | 12–24 months |
| NO₂ | 0–20 or 0–200 ppm | ±2 % FS | electrochemical | 12–24 months |
Technical specifications
| Parameter | Value |
|---|---|
| Measurement time | 2–8 min (min. 6 min for H₂O) |
| Warm-up | 3–4 min at 20 °C, 15 min for full accuracy |
| Inlet pressure | 0.3–35 bar (up to 10 bar in pump-back mode) |
| Pump-back compressor | up to 10 bar, up to 15 cycles per charge at 20 °C |
| Test programmes | IEC and CIGRE, plus custom |
| Display | 7" (178 mm) colour LCD touch screen |
| Printer | built-in thermal printer |
| Memory | 4 GB, about one year of continuous logging |
| Data export | Excel-compatible files to a USB stick |
| Power | lithium battery up to 8 h, 4–6 h charge, mains 90–260 V |
| Operating conditions | -10 to +40 °C, 10–90 % RH |
| Housing | IP66 Peli case with trolley and handles |
| Dimensions | 270 × 560 × 450 mm (H × W × D) |
| Weight | 21 kg with case |
QU4D or a dedicated model?
| Equipment fleet | Model |
|---|---|
| SF6 only | Rapidox SF6 6100 Pump Back |
| g3 and AirPlus only | Rapidox 6100 C4-FN & C5-FK |
| Clean Air only | Rapidox 6100 Clean Air |
| Mixed, or planning a move to alternative gases | Rapidox 6100 QU4D |
Supply in Kazakhstan
KEG TRK supplies Cambridge Sensotec analysers to power utilities and service contractors. We help select the sensor set for your GIS and breaker fleet and the adaptors for your apparatus. Price on request.
Technical specifications
| Gas configuration | SF6 + CF4; C4-FN + CO₂/O₂; C5-FK + CO₂; Clean Air (N₂ + O₂) |
| Gas purity | SF6 0–100 %, ±0.5 % (IR or density) |
| Moisture (dew point) | -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp |
| Decomposition products | SO₂ up to 2000 ppm, HF up to 20 ppm, H₂S up to 100 ppm, CO up to 5000 ppm, NO₂ up to 200 ppm |
| C4-FN (Novec 4710) | C4-FN / C5-FK 0–20 %, ±0.5 % |
| CO₂ (carbon dioxide) | 0–100 %, ±0.5 % (IR) |
| O₂ / air | 0–30 % O₂ / 0–100 % air, ±1 % FS |
| Measurement time | 2–8 min (min. 6 min for H₂O) |
| Pump | pump-back compressor up to 10 bar, up to 15 cycles per charge |
| Pressure | 0.3–35 bar inlet (up to 10 bar in pump-back mode) |
| Display | 7" (178 mm) colour LCD touch screen |
| Battery | lithium, up to 8 hours, 4–6 h charge |
| Protection | IP66 Peli case with trolley |
| Weight | 21 kg (instrument with case) |
| Dimensions | 270 × 560 × 450 mm (H × W × D) |
Applications
Manufacturer
Cambridge Sensotec
One portable pump-back analyser for four insulation types: SF6, C4-FN, C5-FK and Clean Air. Purity, moisture and decomposition products in 2–8 minutes, with IEC and CIGRE test configurations built in.
Key specifications
- Gas configuration
- SF6 + CF4; C4-FN + CO₂/O₂; C5-FK + CO₂; Clean Air (N₂ + O₂)
- Gas purity
- SF6 0–100 %, ±0.5 % (IR or density)
- Moisture (dew point)
- -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp
- Decomposition products
- SO₂ up to 2000 ppm, HF up to 20 ppm, H₂S up to 100 ppm, CO up to 5000 ppm, NO₂ up to 200 ppm
- C4-FN (Novec 4710)
- C4-FN / C5-FK 0–20 %, ±0.5 %
Official supplier in Kazakhstan
Related products

Rapidox 6100 C4-FN & C5-FK Multi-Gas Pumpback — Analyser for SF6-Alternative Gas Mixtures
Portable automatic pump-back analyser for C4-FN (g3, Novec 4710) and C5-FK (AirPlus, Novec 5110) mixtures with CO₂ and O₂. Purity, moisture and CO in 2–8 minutes with no gas released to atmosphere.
- 7" (178 mm) colour LCD touch screen
- 0–20 %, ±0.5 % (IR sensor)

Rapidox 6100 Clean Air Pumpback — Clean Air Insulation Gas Analyser
Portable pump-back analyser for Clean Air insulated equipment (N₂ and O₂ blend): composition, moisture and NO₂ in 2–8 minutes without the sample touching ambient air.
- 0–30 % O₂ / 0–100 % air, ±1 % FS (electrochemical)
- -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp

Rapidox SF6 6100 MK2 Pump Back — SF6 Analyser with Gas Return
Fully automatic zero-emissions SF6 analyser: purity, moisture and decomposition products in 2–8 minutes, then a compressor returns the gas to the equipment at up to 10 bar. Three calibrations for cold, warm and hot climates.
- SF6 0–100 %, ±0.5 % (IR or density)
- -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp

Rapidox SF6 Gas Recovery Bag — Bag for Collecting SF6 After Analysis
80-litre bag for collecting SF6 after analysis: self-sealing couplings, 0.2 bar safety relief valve, heavy-duty PU-coated polyamide. Compatible with the Rapidox SF6 6100 Portable and Bench.
- up to 80 L
- max 0.24 bar; relief valve 0.2 bar; vacuum to -50 mbar

SF6 Hose Connection Kit - Insulating Gas Hose Connection Set
Universal RECTUS 21 adapter kit for connecting SF6 gas analyzers to Siemens, ABB, Hitachi, Schneider, GE and Mitsubishi equipment, in an impact-resistant IP65 case
- SF6 auxiliary equipment
- RECTUS 21 (Series 21) — industry standard
Need advice?
Our specialists will help you choose the optimal Rapidox 6100 QU4D Multi-Gas Pumpback — SF6, C4-FN, C5-FK and Clean Air Analyser configuration for your equipment.
Related articles
All articles →
Integrated Monitoring of CHP Transformer Bays: Rapidox, Vibration and Ultrasound
A CHP transformer bay is transformer, breakers, cooling and switchgear in one reliability loop. How to unify Rapidox (SF₆, O₂, Clean Air), Bently on oil pumps and SDT for partial discharges in one procedure.

Oxygen Depletion in Enclosed MV Switchgear: O₂ and SF₆ Monitoring at CHP Substations
SF₆ leaks in enclosed switchgear displace oxygen below safe levels with no smell or visible warning. How to combine SF₆ and O₂ monitoring with Rapidox at combined heat and power substations.
Clean Air and Oxygen in SF₆-Free Switchgear: Monitoring at CHP During the SF₆ Transition
New dry-air (Clean Air) switchgear at CHP plants needs O₂, humidity and purity control. Rapidox 6100 Clean Air Pumpback for mixed SF₆ and SF₆-free fleets.

Vibration Monitoring of Power Transformer Cooling Auxiliaries at CHP Plants
Oil pumps, radiator fans and water-cooling pumps on step-up transformers are a hidden CHP outage source. Bently Nevada 3500/42M, Orbit DCM and 1900/65A for transformer yard auxiliaries.

Transformer DGA at CHP: What to Add Beyond Oil Chromatography
Dissolved gas analysis (DGA) is the gold standard for transformer diagnosis but not the only tool. Companion methods at CHP plants: cooling vibration, PD ultrasound, SF₆ and O₂ on adjacent switchgear.