Cambridge SensotecSF6 Monitoring

Rapidox SF6 Fixed Detection System — Permanent SF6 Leak Monitoring for Rooms

Continuous SF6 leak monitoring for GIS rooms and substations: an Oldham MX32 or MX43 panel with 1 to 8 OLCT-XPIR infrared detectors (0–2,000 ppm SF6), strobe and horn alarms.

Rapidox SF6 Fixed Detection System — Permanent SF6 Leak Monitoring for Rooms — Cambridge Sensotec
Rapidox SF6 Fixed Detection System — Permanent SF6 Leak Monitoring for Rooms

Supply in Kazakhstan

KEG TRK supplies SF6 gas analysis solutions (Cambridge Sensotec) across Kazakhstan: Almaty, Astana, Karaganda, Ust-Kamenogorsk, Aktobe and other regions. Official warranty, monitoring system design, installation, commissioning and personnel training.

Key features

1 to 8 detectors per panel
OLCT-XPIR infrared detectors, 0–2,000 ppm SF6, ATEX rated
INSTANT, STEL and TWA thresholds per detector
Five programmable alarms, strobe and horn
Relay outputs for external sirens and ventilation
RS485 Modbus RTU and analogue outputs for PLC and BMS
Optional battery backup for power outages

Industry solutions, landing pages and articles about Rapidox SF6 Fixed Detection System — Permanent SF6 Leak Monitoring for Rooms

Typical tasks

  • GIS rooms
  • Indoor substations with SF6 circuit breakers
  • Cable basements and pits below floor level
  • SF6 cylinder stores and reclaim areas
  • Test laboratories

Permanent SF6 leak and atmosphere monitoring system for personnel safety and environmental compliance.

Overview

The Rapidox SF6 Fixed Detection System is a Cambridge Sensotec solution for continuous SF6 leak monitoring in rooms with high voltage GIS, circuit breakers and transformers. SF6 in such equipment is at high pressure, so a leak must be detected immediately, not on the next scheduled round.

The system is built from Oldham Gas components: an MX32 or MX43 wall-mount panel and OLCT-XPIR infrared SF6 detectors. Detectors sit low on the walls; the panel shows the concentration at each one and triggers alarms when thresholds are exceeded.

Why SF6 leaks need continuous monitoring

  • Heavier than air. About five times. A leak flows down and collects at floor level, in pits and cable trenches, where it can displace oxygen.
  • Decomposition products. If the leak comes from an apparatus that has seen arcing or discharge, toxic SO₂, HF and other compounds enter the room.
  • Limits. The shift time-weighted average limit (TLV-TWA) for SF6 is 1,000 ppm; detectors cover up to 2,000 ppm.
  • Environment and losses. An early alarm lets you find and fix the leak before significant gas is lost.

System components

Component Purpose
Oldham MX32 panel controller for 1–2 detectors, lockable toggle latch
Oldham MX43 panel controller for 1–8 detectors, LED bars by zone
Oldham OLCT-XPIR SF6 detector long-life IR sensor, 4–20 mA, ATEX, 0–2,000 ppm
Strobe and horn included with the panel
Battery backup optional, for operation during power cuts
SD card optional data storage

Each detector has programmable INSTANT, STEL (short-term exposure) and TWA (time-weighted average) thresholds.

Alarms and integration

  • five programmable alarm levels;
  • strobe and horn on the panel;
  • a programmable relay per channel plus a separate fault relay;
  • relays drive external sirens or ventilation, or signal existing alarm equipment;
  • RS485 Modbus RTU and analogue outputs for PLC, SCADA or building management;
  • large backlit graphic display with multi-language menus.

Technical specifications

Parameter Value
Detectors MX32: 1–2; MX43: 1–8
Detector range 0–2,000 ppm SF6
Detector type infrared, 4–20 mA, ATEX
Measurement continuous on-line
Power 100–240 V AC or 21–28 V DC
Backup optional battery
Operating temperature -20 to +50 °C
Panel enclosure wall-mount, IP55
MX32 dimensions 265 × 266 × 96 mm
MX43 dimensions 370 × 299 × 109 mm
Weight MX32 1.8 kg; MX43 4 kg
Calibration annually on site

Design and installation

Every room differs in layout, gas volume and ventilation, so the number and position of detectors come from a design. Cambridge Sensotec offers design and installation; KEG TRK helps collect site data, select the configuration and arrange supply to Kazakhstan.

Portable analysers to find the source

The fixed system tells you SF6 is rising in the room. To find the specific apparatus and check its gas, use the portable Rapidox SF6 6100 or Rapidox SF6 6100 Pump Back.

Supply in Kazakhstan

KEG TRK supplies Cambridge Sensotec equipment to power utilities and industrial sites. Price depends on the number of detectors and system scope and is quoted on request.

Manufacturer

Cambridge Sensotec

SF6 Monitoring

Continuous SF6 leak monitoring for GIS rooms and substations: an Oldham MX32 or MX43 panel with 1 to 8 OLCT-XPIR infrared detectors (0–2,000 ppm SF6), strobe and horn alarms.

Key specifications

System
MX32 panel (1–2 detectors) or MX43 (1–8 detectors)
Sensor
Oldham OLCT-XPIR SF6, infrared, 4–20 mA, ATEX
Range
0–2,000 ppm SF6
Alarm
5 programmable alarms, INSTANT / STEL / TWA, strobe and horn
Relays
programmable relay per channel, fault relay

Official supplier in Kazakhstan

Related products

Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser
Cambridge Sensotec

Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser

Lightweight (8.5 kg) SF6 analyser for medium and high voltage GIS and breakers: purity, moisture and decomposition products, up to 8 gases at once. The sample is collected in a bag, not vented.

  • SF6 0–100 %, ±0.5 % (IR)
  • -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp
Price on requestLearn more
Rapidox SF6 6100 MK2 Pump Back — SF6 Analyser with Gas Return
Cambridge Sensotec

Rapidox SF6 6100 MK2 Pump Back — SF6 Analyser with Gas Return

Fully automatic zero-emissions SF6 analyser: purity, moisture and decomposition products in 2–8 minutes, then a compressor returns the gas to the equipment at up to 10 bar. Three calibrations for cold, warm and hot climates.

  • SF6 0–100 %, ±0.5 % (IR or density)
  • -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp
Price on requestLearn more
Rapidox SF6 6100 Bench — Benchtop and Rack-Mount SF6 Analyser
Cambridge Sensotec

Rapidox SF6 6100 Bench — Benchtop and Rack-Mount SF6 Analyser

Fixed SF6 analyser for laboratories, factories and test bays: benchtop or 19" rack. Purity, moisture and decomposition products, 4–20 mA and 0–10 V outputs, alarm relays, RS232/RS485 and Modbus.

  • SF6 0–100 %, ±0.5 % FS
  • -60 to +20 °Cdp, ±2 °Cdp
Price on requestLearn more
Rapidox SF6 Gas Recovery Bag — Bag for Collecting SF6 After Analysis
Cambridge Sensotec

Rapidox SF6 Gas Recovery Bag — Bag for Collecting SF6 After Analysis

80-litre bag for collecting SF6 after analysis: self-sealing couplings, 0.2 bar safety relief valve, heavy-duty PU-coated polyamide. Compatible with the Rapidox SF6 6100 Portable and Bench.

  • up to 80 L
  • max 0.24 bar; relief valve 0.2 bar; vacuum to -50 mbar
Price on requestLearn more

Need advice?

Our specialists will help you choose the optimal Rapidox SF6 Fixed Detection System — Permanent SF6 Leak Monitoring for Rooms configuration for your equipment.

Related articles

All articles →
Transformer DGA at CHP: What to Add Beyond Oil Chromatography
Article

Transformer DGA at CHP: What to Add Beyond Oil Chromatography

Dissolved gas analysis (DGA) is the gold standard for transformer diagnosis but not the only tool. Companion methods at CHP plants: cooling vibration, PD ultrasound, SF₆ and O₂ on adjacent switchgear.

Integrated Monitoring of CHP Transformer Bays: Rapidox, Vibration and Ultrasound
Application

Integrated Monitoring of CHP Transformer Bays: Rapidox, Vibration and Ultrasound

A CHP transformer bay is transformer, breakers, cooling and switchgear in one reliability loop. How to unify Rapidox (SF₆, O₂, Clean Air), Bently on oil pumps and SDT for partial discharges in one procedure.

Oxygen Depletion in Enclosed MV Switchgear: O₂ and SF₆ Monitoring at CHP Substations
Article

Oxygen Depletion in Enclosed MV Switchgear: O₂ and SF₆ Monitoring at CHP Substations

SF₆ leaks in enclosed switchgear displace oxygen below safe levels with no smell or visible warning. How to combine SF₆ and O₂ monitoring with Rapidox at combined heat and power substations.

Article

Clean Air and Oxygen in SF₆-Free Switchgear: Monitoring at CHP During the SF₆ Transition

New dry-air (Clean Air) switchgear at CHP plants needs O₂, humidity and purity control. Rapidox 6100 Clean Air Pumpback for mixed SF₆ and SF₆-free fleets.

Vibration Monitoring of Power Transformer Cooling Auxiliaries at CHP Plants
Application

Vibration Monitoring of Power Transformer Cooling Auxiliaries at CHP Plants

Oil pumps, radiator fans and water-cooling pumps on step-up transformers are a hidden CHP outage source. Bently Nevada 3500/42M, Orbit DCM and 1900/65A for transformer yard auxiliaries.

SF6 Leak Detector or Gas Analyzer: Which One Does Substation Maintenance Need
Article

SF6 Leak Detector or Gas Analyzer: Which One Does Substation Maintenance Need

We break down the difference between an SF6 leak detector (sniffer) and a gas analyzer: when each instrument is needed, how they complement each other, and what modern tenders require.

Часто задаваемые вопросы