Industry solutions, landing pages and articles about Rapidox SF6 Fixed Detection System — Permanent SF6 Leak Monitoring for Rooms
Where it is used
Typical tasks
- GIS rooms
- Indoor substations with SF6 circuit breakers
- Cable basements and pits below floor level
- SF6 cylinder stores and reclaim areas
- Test laboratories
Permanent SF6 leak and atmosphere monitoring system for personnel safety and environmental compliance.
Overview
The Rapidox SF6 Fixed Detection System is a Cambridge Sensotec solution for continuous SF6 leak monitoring in rooms with high voltage GIS, circuit breakers and transformers. SF6 in such equipment is at high pressure, so a leak must be detected immediately, not on the next scheduled round.
The system is built from Oldham Gas components: an MX32 or MX43 wall-mount panel and OLCT-XPIR infrared SF6 detectors. Detectors sit low on the walls; the panel shows the concentration at each one and triggers alarms when thresholds are exceeded.
Why SF6 leaks need continuous monitoring
- Heavier than air. About five times. A leak flows down and collects at floor level, in pits and cable trenches, where it can displace oxygen.
- Decomposition products. If the leak comes from an apparatus that has seen arcing or discharge, toxic SO₂, HF and other compounds enter the room.
- Limits. The shift time-weighted average limit (TLV-TWA) for SF6 is 1,000 ppm; detectors cover up to 2,000 ppm.
- Environment and losses. An early alarm lets you find and fix the leak before significant gas is lost.
System components
| Component | Purpose |
|---|---|
| Oldham MX32 panel | controller for 1–2 detectors, lockable toggle latch |
| Oldham MX43 panel | controller for 1–8 detectors, LED bars by zone |
| Oldham OLCT-XPIR SF6 detector | long-life IR sensor, 4–20 mA, ATEX, 0–2,000 ppm |
| Strobe and horn | included with the panel |
| Battery backup | optional, for operation during power cuts |
| SD card | optional data storage |
Each detector has programmable INSTANT, STEL (short-term exposure) and TWA (time-weighted average) thresholds.
Alarms and integration
- five programmable alarm levels;
- strobe and horn on the panel;
- a programmable relay per channel plus a separate fault relay;
- relays drive external sirens or ventilation, or signal existing alarm equipment;
- RS485 Modbus RTU and analogue outputs for PLC, SCADA or building management;
- large backlit graphic display with multi-language menus.
Technical specifications
| Parameter | Value |
|---|---|
| Detectors | MX32: 1–2; MX43: 1–8 |
| Detector range | 0–2,000 ppm SF6 |
| Detector type | infrared, 4–20 mA, ATEX |
| Measurement | continuous on-line |
| Power | 100–240 V AC or 21–28 V DC |
| Backup | optional battery |
| Operating temperature | -20 to +50 °C |
| Panel enclosure | wall-mount, IP55 |
| MX32 dimensions | 265 × 266 × 96 mm |
| MX43 dimensions | 370 × 299 × 109 mm |
| Weight | MX32 1.8 kg; MX43 4 kg |
| Calibration | annually on site |
Design and installation
Every room differs in layout, gas volume and ventilation, so the number and position of detectors come from a design. Cambridge Sensotec offers design and installation; KEG TRK helps collect site data, select the configuration and arrange supply to Kazakhstan.
Portable analysers to find the source
The fixed system tells you SF6 is rising in the room. To find the specific apparatus and check its gas, use the portable Rapidox SF6 6100 or Rapidox SF6 6100 Pump Back.
Supply in Kazakhstan
KEG TRK supplies Cambridge Sensotec equipment to power utilities and industrial sites. Price depends on the number of detectors and system scope and is quoted on request.
Technical specifications
| System | MX32 panel (1–2 detectors) or MX43 (1–8 detectors) |
| Sensor | Oldham OLCT-XPIR SF6, infrared, 4–20 mA, ATEX |
| Range | 0–2,000 ppm SF6 |
| Alarm | 5 programmable alarms, INSTANT / STEL / TWA, strobe and horn |
| Relays | programmable relay per channel, fault relay |
| Communication | RS485 Modbus RTU, analogue outputs, external relays |
| Storage | optional SD card |
| Power | 100–240 V AC or 21–28 V DC, optional battery |
| Operating temperature | -20 to +50 °C |
| Protection | IP55 wall-mount enclosure |
| Dimensions | MX32: 265 × 266 × 96 mm; MX43: 370 × 299 × 109 mm |
| Weight | MX32: 1.8 kg; MX43: 4 kg |
Applications
Manufacturer
Cambridge Sensotec
Continuous SF6 leak monitoring for GIS rooms and substations: an Oldham MX32 or MX43 panel with 1 to 8 OLCT-XPIR infrared detectors (0–2,000 ppm SF6), strobe and horn alarms.
Key specifications
- System
- MX32 panel (1–2 detectors) or MX43 (1–8 detectors)
- Sensor
- Oldham OLCT-XPIR SF6, infrared, 4–20 mA, ATEX
- Range
- 0–2,000 ppm SF6
- Alarm
- 5 programmable alarms, INSTANT / STEL / TWA, strobe and horn
- Relays
- programmable relay per channel, fault relay
Official supplier in Kazakhstan
Related products

Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser
Lightweight (8.5 kg) SF6 analyser for medium and high voltage GIS and breakers: purity, moisture and decomposition products, up to 8 gases at once. The sample is collected in a bag, not vented.
- SF6 0–100 %, ±0.5 % (IR)
- -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp

Rapidox SF6 6100 MK2 Pump Back — SF6 Analyser with Gas Return
Fully automatic zero-emissions SF6 analyser: purity, moisture and decomposition products in 2–8 minutes, then a compressor returns the gas to the equipment at up to 10 bar. Three calibrations for cold, warm and hot climates.
- SF6 0–100 %, ±0.5 % (IR or density)
- -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp

Rapidox SF6 6100 Bench — Benchtop and Rack-Mount SF6 Analyser
Fixed SF6 analyser for laboratories, factories and test bays: benchtop or 19" rack. Purity, moisture and decomposition products, 4–20 mA and 0–10 V outputs, alarm relays, RS232/RS485 and Modbus.
- SF6 0–100 %, ±0.5 % FS
- -60 to +20 °Cdp, ±2 °Cdp

Rapidox SF6 Gas Recovery Bag — Bag for Collecting SF6 After Analysis
80-litre bag for collecting SF6 after analysis: self-sealing couplings, 0.2 bar safety relief valve, heavy-duty PU-coated polyamide. Compatible with the Rapidox SF6 6100 Portable and Bench.
- up to 80 L
- max 0.24 bar; relief valve 0.2 bar; vacuum to -50 mbar
Need advice?
Our specialists will help you choose the optimal Rapidox SF6 Fixed Detection System — Permanent SF6 Leak Monitoring for Rooms configuration for your equipment.
Related articles
All articles →
Transformer DGA at CHP: What to Add Beyond Oil Chromatography
Dissolved gas analysis (DGA) is the gold standard for transformer diagnosis but not the only tool. Companion methods at CHP plants: cooling vibration, PD ultrasound, SF₆ and O₂ on adjacent switchgear.

Integrated Monitoring of CHP Transformer Bays: Rapidox, Vibration and Ultrasound
A CHP transformer bay is transformer, breakers, cooling and switchgear in one reliability loop. How to unify Rapidox (SF₆, O₂, Clean Air), Bently on oil pumps and SDT for partial discharges in one procedure.

Oxygen Depletion in Enclosed MV Switchgear: O₂ and SF₆ Monitoring at CHP Substations
SF₆ leaks in enclosed switchgear displace oxygen below safe levels with no smell or visible warning. How to combine SF₆ and O₂ monitoring with Rapidox at combined heat and power substations.
Clean Air and Oxygen in SF₆-Free Switchgear: Monitoring at CHP During the SF₆ Transition
New dry-air (Clean Air) switchgear at CHP plants needs O₂, humidity and purity control. Rapidox 6100 Clean Air Pumpback for mixed SF₆ and SF₆-free fleets.

Vibration Monitoring of Power Transformer Cooling Auxiliaries at CHP Plants
Oil pumps, radiator fans and water-cooling pumps on step-up transformers are a hidden CHP outage source. Bently Nevada 3500/42M, Orbit DCM and 1900/65A for transformer yard auxiliaries.

SF6 Leak Detector or Gas Analyzer: Which One Does Substation Maintenance Need
We break down the difference between an SF6 leak detector (sniffer) and a gas analyzer: when each instrument is needed, how they complement each other, and what modern tenders require.