Cambridge SensotecSF6 Analyzers

Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser

Lightweight (8.5 kg) SF6 analyser for medium and high voltage GIS and breakers: purity, moisture and decomposition products, up to 8 gases at once. The sample is collected in a bag, not vented.

Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser — Cambridge Sensotec
Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser

Supply in Kazakhstan

KEG TRK supplies SF6 gas analysis solutions (Cambridge Sensotec) across Kazakhstan: Almaty, Astana, Karaganda, Ust-Kamenogorsk, Aktobe and other regions. Official warranty, monitoring system design, installation, commissioning and personnel training.

Key features

SF6 purity 0–100 %, ±0.5 % (IR sensor)
Up to 8 gases at once: H₂O, SO₂, HF, H₂S, CO, CF4, air
Rapidri system speeds up repeat dew point readings
Outlet for connecting a gas recovery bag
IEC and CIGRE test configurations
8.5 kg including the IP66 case
Lithium battery, over 8 hours

Industry solutions, landing pages and articles about Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser

Typical tasks

  • GIS and SF6 circuit breakers
  • SF6 current and voltage transformers
  • Gas checks after filling and reclaim
  • Incoming inspection of SF6 cylinders
  • Mobile substation crews

Documentation

Official manufacturer PDF documents. Key specifications are also published on this page.

Need a price with delivery in Kazakhstan? We will prepare a quotation for your task.

Premium portable Rapidox SF6 6100 for on-site quality control of sulfur hexafluoride insulation.

Overview

The Rapidox SF6 6100 Portable is a portable analyser from the British company Cambridge Sensotec for monitoring SF6 quality in medium and high voltage gas-insulated equipment. It is the lightest field model in the range: 8.5 kg including the case.

The instrument measures SF6 purity, moisture and decomposition products. The configuration is modular, with up to eight gases per instrument. Compartment gas pressure is logged together with the results.

Why analyse SF6

Arcing and partial discharge break SF6 down. Decomposition products are toxic and attack insulation, and moisture lowers dielectric strength. Regular analysis finds internal defects before failure, confirms gas quality after filling and helps assess the hazard before a compartment is opened.

SF6 is a greenhouse gas and must not be vented, so the sample from the Rapidox SF6 6100 Portable is collected in a bag.

How a measurement works

  1. Connect with self-sealing tongue-and-groove couplings compatible with major equipment brands.
  2. Gas flows through the analyser on compartment pressure, up to 10 bar. For sources at atmospheric pressure, an optional pump is fitted.
  3. All gases are measured and logged simultaneously; a stable reading takes a few minutes.
  4. The spent sample goes to the gas recovery bag.
  5. Results are printed on the built-in thermal printer and exported to a USB stick.

Sensors and ranges

Parameter Range Accuracy Sensor type Calibration Life span
SF6 0–100 % ±0.5 % IR 12 months over 5 years
H₂O (dew point) -60 to +20 °Cdp (10–24,000 ppmV) ±2 °Cdp polymer 12 months (sensor exchange) 2–3 years
SO₂ 0–100 or 0–500 ppm ±2 % FS electrochemical 12 months 2–3 years
HF 0–10 or 0–30 ppm ±2 % FS electrochemical 12 months 2–3 years
CF4 0–80 % ±1 % of reading calculated not required —
H₂S 0–100 ppm ±2 % FS electrochemical 12 months 2–3 years
CO 0–1000 ppm ±2 % FS electrochemical 12 months 2–3 years
Air / N₂ 0–100 % FS based on oxygen electrochemical 12 months 2–3 years

Technical specifications

Parameter Value
Warm-up 3–4 min at 20 °C
Inlet pressure up to 10 bar
Sample flow 100–1000 mL/min
Pump (optional) 0–1 L/min
Display 7" (180 mm) colour LCD touch screen
Printer integrated thermal printer
Memory 4 GB, about one year of continuous logging
Data export Excel-compatible files to a USB stick
Power lithium battery over 8 h, 4–6 h charge, mains 90–260 V
Operating conditions -10 to +40 °C, 10–90 % RH
Housing heavy-duty IP66 case
Dimensions 180 × 480 × 360 mm (H × W × D)
Weight 8.5 kg with case

Which Rapidox SF6 model to choose

Model Sample handling Weight Best for
Rapidox SF6 6100 Portable into a recovery bag 8.5 kg Mobile crews, occasional testing
Rapidox SF6 6100 Pump Back returned to equipment 20 kg Regular testing with no gas loss
Rapidox SF6 6100 Bench into a bag or recovery system 6.5 kg Laboratories, manufacturing

Supply in Kazakhstan

KEG TRK supplies Cambridge Sensotec analysers to power utilities and substation services. We help select the sensor set and couplings for your apparatus. Price on request.

Manufacturer

Cambridge Sensotec

SF6 Analyzers

Lightweight (8.5 kg) SF6 analyser for medium and high voltage GIS and breakers: purity, moisture and decomposition products, up to 8 gases at once. The sample is collected in a bag, not vented.

Key specifications

Gas purity
SF6 0–100 %, ±0.5 % (IR)
Moisture (dew point)
-60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp
Decomposition products
SO₂ 0–100/500 ppm, HF 0–10/30 ppm, H₂S 0–100 ppm, CO 0–1000 ppm, CF4 0–80 %
Pressure
up to 10 bar inlet
Pump
optional pump 0–1 L/min

Official supplier in Kazakhstan

Related products

Rapidox SF6 6100 MK2 Pump Back — SF6 Analyser with Gas Return
Cambridge Sensotec

Rapidox SF6 6100 MK2 Pump Back — SF6 Analyser with Gas Return

Fully automatic zero-emissions SF6 analyser: purity, moisture and decomposition products in 2–8 minutes, then a compressor returns the gas to the equipment at up to 10 bar. Three calibrations for cold, warm and hot climates.

  • SF6 0–100 %, ±0.5 % (IR or density)
  • -60 to +20 °Cdp (10–24,000 ppmV), ±2 °Cdp
Price on requestLearn more
Rapidox SF6 6100 Bench — Benchtop and Rack-Mount SF6 Analyser
Cambridge Sensotec

Rapidox SF6 6100 Bench — Benchtop and Rack-Mount SF6 Analyser

Fixed SF6 analyser for laboratories, factories and test bays: benchtop or 19" rack. Purity, moisture and decomposition products, 4–20 mA and 0–10 V outputs, alarm relays, RS232/RS485 and Modbus.

  • SF6 0–100 %, ±0.5 % FS
  • -60 to +20 °Cdp, ±2 °Cdp
Price on requestLearn more
Rapidox 6100 QU4D Multi-Gas Pumpback — SF6, C4-FN, C5-FK and Clean Air Analyser
Cambridge Sensotec

Rapidox 6100 QU4D Multi-Gas Pumpback — SF6, C4-FN, C5-FK and Clean Air Analyser

One portable pump-back analyser for four insulation types: SF6, C4-FN, C5-FK and Clean Air. Purity, moisture and decomposition products in 2–8 minutes, with IEC and CIGRE test configurations built in.

  • SF6 + CF4; C4-FN + CO₂/O₂; C5-FK + CO₂; Clean Air (N₂ + O₂)
  • SF6 0–100 %, ±0.5 % (IR or density)
Price on requestLearn more
Rapidox SF6 Gas Recovery Bag — Bag for Collecting SF6 After Analysis
Cambridge Sensotec

Rapidox SF6 Gas Recovery Bag — Bag for Collecting SF6 After Analysis

80-litre bag for collecting SF6 after analysis: self-sealing couplings, 0.2 bar safety relief valve, heavy-duty PU-coated polyamide. Compatible with the Rapidox SF6 6100 Portable and Bench.

  • up to 80 L
  • max 0.24 bar; relief valve 0.2 bar; vacuum to -50 mbar
Price on requestLearn more
SF6 Hose Connection Kit - Insulating Gas Hose Connection Set
Cambridge Sensotec

SF6 Hose Connection Kit - Insulating Gas Hose Connection Set

Universal RECTUS 21 adapter kit for connecting SF6 gas analyzers to Siemens, ABB, Hitachi, Schneider, GE and Mitsubishi equipment, in an impact-resistant IP65 case

  • SF6 auxiliary equipment
  • RECTUS 21 (Series 21) — industry standard
Price on requestLearn more

Need advice?

Our specialists will help you choose the optimal Rapidox SF6 6100 Portable — Portable SF6 Gas Analyser configuration for your equipment.

Related articles

All articles →
How to Test SF6 Gas Quality at a Substation: Step-by-Step Guide
Article

How to Test SF6 Gas Quality at a Substation: Step-by-Step Guide

SF6 gas quality is tested with an analyser connected directly to the compartment: SF6 purity, moisture and decomposition products. What to measure, how to connect, what to compare the result with and when to test the gas.

SF6 Moisture Limits: Dew Point, ppmv and How to Measure Water in SF6
Article

SF6 Moisture Limits: Dew Point, ppmv and How to Measure Water in SF6

SF6 moisture is stated in ppmv or as a dew point. The acceptable water content depends on the gas pressure in the equipment. How to convert the units and measure moisture with a Rapidox SF6 6100.

Article

SF6 Decomposition Products: SO2, HF and What to Do About Them

Discharges and arcs break SF6 down into SO2, HF, SOF2, S2F10 and metal fluoride dust. Why they are dangerous, which exposure limits apply and how to measure them with an analyser.

Predictive Maintenance Cuts Equipment Failures by 73%. That Is Not Marketing — It Is Data
Article

Predictive Maintenance Cuts Equipment Failures by 73%. That Is Not Marketing — It Is Data

Fixed maintenance calendars do not stop unplanned downtime: up to 15% of MRO effort is spent on unnecessary work. Sensor-driven predictive maintenance cuts downtime by 30–50% and equipment-related incidents by 40% — on mining, oil & gas and power sites in Kazakhstan and the CIS with Artesis, SDT and Rapidox.

Transformer DGA at CHP: What to Add Beyond Oil Chromatography
Article

Transformer DGA at CHP: What to Add Beyond Oil Chromatography

Dissolved gas analysis (DGA) is the gold standard for transformer diagnosis but not the only tool. Companion methods at CHP plants: cooling vibration, PD ultrasound, SF₆ and O₂ on adjacent switchgear.

Article

Clean Air and Oxygen in SF₆-Free Switchgear: Monitoring at CHP During the SF₆ Transition

New dry-air (Clean Air) switchgear at CHP plants needs O₂, humidity and purity control. Rapidox 6100 Clean Air Pumpback for mixed SF₆ and SF₆-free fleets.

Часто задаваемые вопросы